Monitoring Riello USV with NetMan 204 adapter using snmp

NetMan 204 Network Adapter
> users manual: https://www.riello-ups.com/uploads/file/768/2768/0MNACCSA4ENUL__MAN_ACC_NETMAN_204_EN_.pdf
> mib files can be found, also on riello-ups website: https://www.riello-ups.com/uploads/file/136/1136/MIBs.zip
>> important mib: RFC1628A.MIB

>> short solution:

(1):
use a simple perl script to get data in checkmk format:
https://computer2know.de/checknetman.pl-script-to-get-usv-load-and-power-in-watts-from-a-riello-usv-in-checkmk-agent-format:::656.html

(2):
use a Nagios script
https://exchange.nagios.org/directory/Plugins/Hardware/UPS/SNMP-UPS-Check/details

run it like:

./check_ups_snmp -H 10.115.0.82 -C pnpub -t status
OK: Battery Status Normal.

or

./check_ups_snmp -H 10.115.0.82 -C pnpub -t alarm
OK: 0 alarms present.|'alarms'=0



=====================================================================================================
my detail analysis ....

Doing a snmpwalk on the device:
------------------------------------
snmpwalk -c my-community -v 2c usv-ip-address
SNMPv2-MIB::sysDescr.0 = STRING: NetMan 204
SNMPv2-MIB::sysObjectID.0 = OID: SNMPv2-SMI::enterprises.5491.6
DISMAN-EVENT-MIB::sysUpTimeInstance = Timeticks: (2761455986) 319 days, 14:42:39.86
SNMPv2-MIB::sysContact.0 = STRING: my-organisation
SNMPv2-MIB::sysName.0 = STRING: my-usv-name
SNMPv2-MIB::sysLocation.0 = STRING: my-localtion
SNMPv2-MIB::sysServices.0 = INTEGER: 0
IF-MIB::ifNumber.0 = INTEGER: 1
IF-MIB::ifPhysAddress = STRING: 0:0:0:5:22:99
SNMPv2-SMI::mib-2.33.1.1.1.0 = STRING: "RPS SpA"
SNMPv2-SMI::mib-2.33.1.1.2.0 = STRING: "T2MK20 "
SNMPv2-SMI::mib-2.33.1.1.3.0 = STRING: "SWM022-02-21"
SNMPv2-SMI::mib-2.33.1.1.4.0 = STRING: "AppVer. 01.03.010"
SNMPv2-SMI::mib-2.33.1.1.5.0 = STRING: "FT-H 20 kVA "
SNMPv2-SMI::mib-2.33.1.1.6.0 = STRING: "??? "
SNMPv2-SMI::mib-2.33.1.2.1.0 = INTEGER: 2 !!#upsBatteryStatus 2 = should be on batteryNormal
SNMPv2-SMI::mib-2.33.1.2.2.0 = INTEGER: 0 #upsSecondsOnBattery
SNMPv2-SMI::mib-2.33.1.2.3.0 = INTEGER: 60 #upsEstimatedMinutesRemaining
SNMPv2-SMI::mib-2.33.1.2.4.0 = INTEGER: 100 #upsEstimatedChargeRemaining
SNMPv2-SMI::mib-2.33.1.2.5.0 = INTEGER: 2726 #upsBatteryVoltage
SNMPv2-SMI::mib-2.33.1.2.6.0 = INTEGER: 0 #upsBatteryCurrent
SNMPv2-SMI::mib-2.33.1.2.7.0 = INTEGER: 23 !!#upsBatteryTemperature - The ambient temperature at or near the UPS Battery casing.
SNMPv2-SMI::mib-2.33.1.3.1.0 = Counter32: 0
SNMPv2-SMI::mib-2.33.1.3.2.0 = INTEGER: 3
SNMPv2-SMI::mib-2.33.1.3.3.1.1.1 = INTEGER: 1 #upsInputLineBads
SNMPv2-SMI::mib-2.33.1.3.3.1.1.2 = INTEGER: 2 #upsInputNumLines
SNMPv2-SMI::mib-2.33.1.3.3.1.1.3 = INTEGER: 3 #upsInputTable
SNMPv2-SMI::mib-2.33.1.3.3.1.2.1 = INTEGER: 500 #upsInputFrequency -- UNITS 0.1 Hertz
SNMPv2-SMI::mib-2.33.1.3.3.1.2.2 = INTEGER: 500 #upsInputFrequency -- UNITS 0.1 Hertz
SNMPv2-SMI::mib-2.33.1.3.3.1.2.3 = INTEGER: 500 #upsInputFrequency -- UNITS 0.1 Hertz
SNMPv2-SMI::mib-2.33.1.3.3.1.3.1 = INTEGER: 232 #upsInputVoltage
SNMPv2-SMI::mib-2.33.1.3.3.1.3.2 = INTEGER: 233 #upsInputVoltage
SNMPv2-SMI::mib-2.33.1.3.3.1.3.3 = INTEGER: 232 #upsInputVoltage
SNMPv2-SMI::mib-2.33.1.3.3.1.4.1 = INTEGER: -1 #upsInputCurrent
SNMPv2-SMI::mib-2.33.1.3.3.1.4.2 = INTEGER: -1 #upsInputCurrent
SNMPv2-SMI::mib-2.33.1.3.3.1.4.3 = INTEGER: -1 #upsInputCurrent
SNMPv2-SMI::mib-2.33.1.3.3.1.5.1 = INTEGER: 0 #upsInputTruePower
SNMPv2-SMI::mib-2.33.1.3.3.1.5.2 = INTEGER: 0 #upsInputTruePower
SNMPv2-SMI::mib-2.33.1.3.3.1.5.3 = INTEGER: 0 #upsInputTruePower
SNMPv2-SMI::mib-2.33.1.4.1.0 = INTEGER: 3 !!#upsOutputSource 3 = normal
SNMPv2-SMI::mib-2.33.1.4.2.0 = INTEGER: 500 #upsOutputFrequency -- UNITS 0.1 Hertz
SNMPv2-SMI::mib-2.33.1.4.3.0 = INTEGER: 3 #upsOutputNumLines
SNMPv2-SMI::mib-2.33.1.4.4.1.1.1 = INTEGER: 1 #upsOutputLineIndex >> 3 out put lines!
SNMPv2-SMI::mib-2.33.1.4.4.1.1.2 = INTEGER: 2 #upsOutputLineIndex
SNMPv2-SMI::mib-2.33.1.4.4.1.1.3 = INTEGER: 3 #upsOutputLineIndex
SNMPv2-SMI::mib-2.33.1.4.4.1.2.1 = INTEGER: 230 #upsOutputVoltage
SNMPv2-SMI::mib-2.33.1.4.4.1.2.2 = INTEGER: 230 #upsOutputVoltage
SNMPv2-SMI::mib-2.33.1.4.4.1.2.3 = INTEGER: 230 #upsOutputVoltage
SNMPv2-SMI::mib-2.33.1.4.4.1.3.1 = INTEGER: 110 #upsOutputCurrent -- UNITS 0.1 RMS Amp
SNMPv2-SMI::mib-2.33.1.4.4.1.3.2 = INTEGER: 75 #upsOutputCurrent -- UNITS 0.1 RMS Amp
SNMPv2-SMI::mib-2.33.1.4.4.1.3.3 = INTEGER: 23 #upsOutputCurrent -- UNITS 0.1 RMS Amp
SNMPv2-SMI::mib-2.33.1.4.4.1.4.1 = INTEGER: 2290 !!#upsOutputPower -- UNITS Watts
SNMPv2-SMI::mib-2.33.1.4.4.1.4.2 = INTEGER: 1590 !!#upsOutputPower -- UNITS Watts
SNMPv2-SMI::mib-2.33.1.4.4.1.4.3 = INTEGER: 432 !!#upsOutputPower -- UNITS Watts
SNMPv2-SMI::mib-2.33.1.4.4.1.5.1 = INTEGER: 38 !!#upsOutputPercentLoad
SNMPv2-SMI::mib-2.33.1.4.4.1.5.2 = INTEGER: 26 !!#upsOutputPercentLoad
SNMPv2-SMI::mib-2.33.1.4.4.1.5.3 = INTEGER: 7 !!#upsOutputPercentLoad
SNMPv2-SMI::mib-2.33.1.5.1.0 = INTEGER: 500 #upsBypassFrequency
SNMPv2-SMI::mib-2.33.1.5.2.0 = INTEGER: 3 #upsBypassNumLines
SNMPv2-SMI::mib-2.33.1.5.3.1.1.1 = INTEGER: 1
SNMPv2-SMI::mib-2.33.1.5.3.1.1.2 = INTEGER: 2
SNMPv2-SMI::mib-2.33.1.5.3.1.1.3 = INTEGER: 3
SNMPv2-SMI::mib-2.33.1.5.3.1.2.1 = INTEGER: 232
SNMPv2-SMI::mib-2.33.1.5.3.1.2.2 = INTEGER: 231
SNMPv2-SMI::mib-2.33.1.5.3.1.2.3 = INTEGER: 233
SNMPv2-SMI::mib-2.33.1.5.3.1.3.1 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.5.3.1.3.2 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.5.3.1.3.3 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.5.3.1.4.1 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.5.3.1.4.2 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.5.3.1.4.3 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.6.1.0 = Gauge32: 0 #upsALARM : The present number of active alarm conditions. >> if 0 == No alarms present.
SNMPv2-SMI::mib-2.33.1.6.2.1.1.1 = INTEGER: 1
SNMPv2-SMI::mib-2.33.1.6.2.1.1.2 = INTEGER: 2
SNMPv2-SMI::mib-2.33.1.6.2.1.1.3 = INTEGER: 3
SNMPv2-SMI::mib-2.33.1.6.2.1.1.4 = INTEGER: 4
SNMPv2-SMI::mib-2.33.1.6.2.1.1.5 = INTEGER: 5
SNMPv2-SMI::mib-2.33.1.6.2.1.1.6 = INTEGER: 6
SNMPv2-SMI::mib-2.33.1.6.2.1.1.7 = INTEGER: 7
SNMPv2-SMI::mib-2.33.1.6.2.1.1.8 = INTEGER: 8
SNMPv2-SMI::mib-2.33.1.6.2.1.1.9 = INTEGER: 9
SNMPv2-SMI::mib-2.33.1.6.2.1.1.10 = INTEGER: 10
SNMPv2-SMI::mib-2.33.1.6.2.1.2.1 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.2 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.3 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.4 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.5 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.6 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.7 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.8 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.9 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.2.10 = OID: SNMPv2-SMI::zeroDotZero.0.0.0.0.0.0.0.0.0
SNMPv2-SMI::mib-2.33.1.6.2.1.3.1 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.2 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.3 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.4 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.5 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.6 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.7 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.8 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.9 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.6.2.1.3.10 = Timeticks: (0) 0:00:00.00
SNMPv2-SMI::mib-2.33.1.8.1.0 = INTEGER: -1
SNMPv2-SMI::mib-2.33.1.8.2.0 = INTEGER: -1
SNMPv2-SMI::mib-2.33.1.8.3.0 = INTEGER: -1
SNMPv2-SMI::mib-2.33.1.8.4.0 = INTEGER: -1
SNMPv2-SMI::mib-2.33.1.8.5.0 = INTEGER: -1
SNMPv2-SMI::mib-2.33.1.9.1.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.2.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.3.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.4.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.5.0 = INTEGER: 20000
SNMPv2-SMI::mib-2.33.1.9.6.0 = INTEGER: 18000
SNMPv2-SMI::mib-2.33.1.9.7.0 = INTEGER: 3
SNMPv2-SMI::mib-2.33.1.9.8.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.9.0 = INTEGER: 0
SNMPv2-SMI::mib-2.33.1.9.10.0 = INTEGER: 0



---------------------------------------------------------------------------
- if you want to react on snmp traps
---------------------------------------------------------------------------
SensorTrap.mib:
-- IRMS-MIB { iso org(3) dod(6) internet(1) private(4)
-- enterprises(1) riello(5491) }

SENSORTRAP-MIB DEFINITIONS ::= BEGIN

-- Title: SENSOR TRAP MIB
-- Version: 1.0 by Michele Marcon
-- Date: 02.11.2009

IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;


rielloMIB OBJECT IDENTIFIER ::= { enterprises 5491 }

sensorgroup OBJECT IDENTIFIER ::= { rielloMIB 9 }

sensor OBJECT IDENTIFIER ::= { sensorgroup 1 }

sensorId OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of the sensor."
::= { sensor 1 }

sensorTrapGroup OBJECT IDENTIFIER ::= { sensor 2 }


sensorAlarmTMax TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent each minute when temperature reaches maximum level"
::= 1

sensorAlarmTMaxRemoved TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent when temperature returns to standard level"
::= 2

sensorAlarmTMin TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent each minute when temperature reaches minimum level"
::= 3

sensorAlarmTMinRemoved TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent when temperature returns to standard level"
::= 4

sensorIOAlarm TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent each minute when input contact is in alarm"
::= 5

sensorIOAlarmRemoved TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent when input contact is normal"
::= 6

sensorHumidityAlarm TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent each minute when humidity reaches maximum level"
::= 7

sensorHumidityAlarmRemoved TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent when humidity returns to normal level"
::= 8

sensorHumidityLowAlarm TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent each minute when humidity reaches minimum level"
::= 9

sensorHumidityLowAlarmRemoved TRAP-TYPE
ENTERPRISE sensorTrapGroup
VARIABLES { sensorId }
DESCRIPTION "This trap is sent when humidity returns to normal level"
::= 10

END

computer2know :: thank you for your visit :: have a nice day :: © 2024